Ngenjongo yokubonelela ngesisombululo sokupholisa , ukusebenza okuqhelekileyo kwe-industrial chiller yinto ebalulekileyo ngaphambi kokuba izixhobo zoomatshini zisebenze ngokuzinzileyo. Kwaye ukuzinza koxinzelelo luphawu olubalulekileyo lokulinganisa ukuba iyunithi yokufriji isebenza ngokuqhelekileyo na . Xa uxinzelelo olukwi- water chiller luphezulu kakhulu, luya kubangela isignali yempazamo ethumela i-alamu kwaye luyekise inkqubo yokufriji ukuba isebenze. Sinokubona ngokukhawuleza kwaye sisombulule ingxaki kwezi zinto zilandelayo:
1. Ubushushu obuphezulu kakhulu obubangelwa kukungasasazeki kakuhle kobushushu
Ukuvaleka kwegauze yesihluzo kuya kubangela ukuba ubushushu bungabi buninzi. Ukusombulula le ngxaki, ungayisusa igauze uze uyicoce rhoqo.
Ukugcina umoya ungena kakuhle kwindawo yokungena neyokuphuma kubalulekile ekuchitheni ubushushu.
2. I-condenser evalekileyo
Ukuvaleka kwe-condenser kunokubangela ukungasebenzi kakuhle koxinzelelo oluphezulu kwinkqubo yokupholisa kangangokuba igesi efrijini enoxinzelelo oluphezulu ijika ibe yingxinano engaqhelekanga kwaye inani elikhulu legesi liqokelelana. Ngoko ke kuyimfuneko ukucoca rhoqo kwi-condenser, enemiyalelo yokucoca efumaneka kwiqela le-S&A emva kokuthengisa nge-imeyile.
3. Ifriji egqithisileyo
I-refrigerant engaphezulu ayinakujiya ibe lulwelo ize igqume indawo, nto leyo enciphisa isiphumo sokujiya kwaye ngaloo ndlela yonyusa uxinzelelo. I-refrigerant kufuneka ikhutshwe ide ibe yesiqhelo ngokwe-suck and exhaust pressure, i-balance pressure kunye ne-running current phantsi kweemeko zokusebenza ezilinganisiweyo.
4. Umoya kwinkqubo yokupholisa
Le meko idla ngokubakho emva kokugcinwa kwecompressor okanye umatshini omtsha apho umoya uxutywa kwinkqubo yokupholisa kwaye uhlala kwi-condenser okubangela ukungaphumeleli kokufuma kunye nokunyuka koxinzelelo. Isisombululo kukukhupha igesi ngevalvu eyahlula umoya, i-outlet yomoya kunye ne-condenser ye-chiller. Ukuba unamathandabuzo malunga nokusebenza, nceda unxibelelane neqela leenkonzo ze-S&A emva kokuthengisa.
5. I-alamu yobuxoki/ipharamitha engaqhelekanga
Ipharamitha ye-Shield okanye i-short circuit umgca wesignali ye-pressure switch, uze uvule i-chiller ukuze ujonge ukuba inkqubo yokupholisa ingasebenza ngokuqhelekileyo na. Nceda uqaphele ukuba ukuba i-alamu ye-E09 ivele, inokugwetywa ngokuthe ngqo njengokungaqheleki kwepharamitha, kwaye kufuneka nje utshintshe ipharamitha.
Ngamava e-R&D eminyaka engama-20 ekwenzeni ii-chiller, i-S&A chiller iphuhlise ulwazi olunzulu ngee-chiller zamanzi zoshishino, iyazingca ngeenjineli ezibalaseleyo ezinoxanduva lokufumanisa nokulungisa iimpazamo, kwaye inkonzo yokuphendula ngokukhawuleza emva kokuthengisa iqinisekisa abathengi bethu xa bethenga kwaye besebenzisa.
![Umthamo wokupholisa we-Industrial Recirculating Chiller CW-6100 4200W]()