Ngenjongo yokubonelela
isisombululo sokupholisa
, ukusebenza okuqhelekileyo kwe-industrial chiller yimeko eyimfuneko yokusebenza ngokuzinzileyo kwezixhobo zoomatshini. Kwaye
ukuzinza koxinzelelo luphawu olubalulekileyo lokulinganisa ukuba iyunithi yefriji isebenza ngokuqhelekileyo
. Xa uxinzelelo kwi
chiller amanzi
iphezulu kakhulu, iyakubangela i-alam ithumele umqondiso wempazamo kwaye imise inkqubo yefriji ekusebenzeni. Sinokubona ngokukhawuleza kwaye silungise ukungasebenzi kakuhle kule miba ilandelayo:
1 Ubushushu obuphezulu be-ambient obubangelwa kukuchithwa kobushushu obungalunganga
Ukuvala i-gauze yokucoca kuya kukhokelela kwimitha yokushisa enganelanga. Ukuyicombulula le ngxaki, unokususa i-gauze kwaye uyihlambulule rhoqo.
Ukugcina impepho elungileyo kwindawo yokungena nokuphuma komoya kukwabalulekile ekuchitheni ubushushu.
2 I-condenser evaliweyo
Ukuvaleka kwi-condenser kunokubangela ukungaphumeleli koxinzelelo oluphezulu kwinkqubo yokupholisa ukuba i-high-pressure refrigerant gas iyancipha ngokungaqhelekanga kwaye isixa esikhulu segesi siqokelelane. Ngoko kuyimfuneko ukwenza ukucoca ngamaxesha athile kwi-condenser, imiyalelo yayo yokucoca ifumaneka kwi-S&Iqela emva kokuthengisa nge-imeyile.
3 Ifriji egqithisileyo
Ukugqithiswa kwefriji akukwazi ukudibanisa kwi-liquid kunye nokugubungela indawo, ukunciphisa umphumo wokunciphisa kwaye ngoko kwandisa uxinzelelo. Ifriji kufuneka ikhutshwe de ibe yesiqhelo ngokokufunxa kunye noxinzelelo lwe-exhaust, ibhalansi yoxinzelelo kunye nokuhamba kwangoku phantsi kweemeko zokusebenza ezilinganisiweyo.
4 Umoya kwisixokelelwano sokupholisa
Le meko idla ngokubakho emva kokugcinwa kwecompressor okanye umatshini omtsha ukuba umoya uxutywe kwinkqubo yokupholisa kwaye uhlala kwi-condenser ebangela ukusilela kwe-condensation kunye nokunyuka koxinzelelo. Isisombululo kukususa igas ngokusebenzisa ivalve eyahlula umoya, indawo yokuphuma yomoya kunye necondenser ye chiller. Ukuba unawo nawaphi na amathandabuzo ngolu tyando, nceda uzive ukhululekile ukuqhagamshelana no-S&Iqela lenkonzo emva kokuthengisa.
5 I-alam yobuxoki/iparamitha engaqhelekanga
Shield parameter okanye isekethe emfutshane umgca wophawu loxinzelelo, uze uvule i-chiller ukujonga ukuba
inkqubo yokupholisa
inokusebenza ngokuqhelekileyo. Nceda uqaphele ukuba i-alamu ye-E09 yenzeka, inokugwetywa ngokuthe ngqo njenge-parameter engaqhelekanga, kwaye kufuneka uguqule iparameter.
Ngeminyaka engama-20 ye-R&Amava e-D kwimveliso ye-chiller,
S&Umntu opholileyo
iphuhlise ulwazi olunzulu lwezixhobo zokupholisa amanzi kwimizi-mveliso, iqhayisa ngeenjineli ezibalaseleyo ezinoxanduva lokubona iimpazamo kunye nokugcinwa kwazo, kunye nenkonzo yokusabela ngokukhawuleza emva kokuthengisa iqinisekisa abathengi bethu xa kuthengwa kwaye kusetyenziswa.