I-SGS-Tested fibre Laser Chiller CWFL-12000KNPTY-UL

I-UL & CSA Compliant Industrial Chiller yezinhlelo ze-Fiber Laser ezingu-12kW

TEYU I-CWFL-12000KNPTY-UL industrial chiller yenzelwe izinhlelo ze-fiber laser ezingu-12kW, inikeza amandla okupholisa angu-35kW anezisekethe zokupholisa ezizimele ezimbili ukuze kuphathwe ukushisa okunembile. Ihlolwe ngokuzimela yi-SGS kuya kumazinga e-UL kanye ne-CSA, isekela izidingo zikagesi zaseNyakatho Melika futhi inikeza ukupholisa okuthembekile kwezicelo ze-laser yezimboni ezinamandla aphezulu.


Ifakwe ngokulawula izinga lokushisa okubili okuhlakaniphile, ukuxhumana kwe-RS-485 Modbus RTU, kanye nokuvikelwa kwamazinga amaningi, TEYU CWFL-12000KNPTY-UL ifaneleka kahle emigqeni yokukhiqiza ezenzakalelayo kanye nezindawo zokukhiqiza ezihlakaniphile. Isiza ekuthuthukiseni ukuthembeka kwemishini, ukunciphisa isikhathi sokungasebenzi, kanye nokusekela ukusebenza okuqhubekayo kwesikhathi eside.

Product characteristics

Product Parameters

ImodeliCWFL-12000KNPTY-UL I-voltageAC 3P 460V~480V
Imvamisa 60Hz Okwamanje3.7~28.4 A
Ukusetshenziswa kwamandla okuphezulu 19.3kW Amandla e-heater600W+3600W
Umthamo wokupholisa ojwayelekile 119424Btu/h IsiqandisiR-32
35kW Ukunemba ±1℃
30094Kcal/h Isinciphisi I-Capillary
Amandla ephampu 3kW Umthamo wethangi170L
Ukungena kanye nokukhipha Rp1/2"+Rp1-1/4” Umfutho ophezulu wephampu Ibha engu-6
Ukugeleza okulinganiselwe 2.5L/min+ >133Lmin Ubukhulu 145 × 80 × 132cm(L × W × H)
N.W. 290kg Ubukhulu bephakheji 147 × 92 × 150cm(L × W × H)
G.W. 333kg

Product Features

Precise Temperature Control
Delivers stable and accurate cooling performance to prevent overheating and ensure consistent processing quality.
Efficient Cooling System
Uses advanced compressors and heat exchangers for fast heat dissipation under high-load conditions.
Real-Time Monitoring & Alarms
Features a smart display with real-time monitoring and fault alarms to ensure safe operation.
Energy Efficient Design
Incorporates energy-saving components to minimize power usage while maintaining strong cooling efficiency.
Compact & Easy Operation
Compact design fits tight spaces, with intuitive controls for quick setup and simple daily use.
Certified for Global Standards
Complies with international safety and quality certifications for reliable use across global industries.
Durable & Highly Reliable
Constructed with robust materials and safety alarms for continuous, long-term, and stable performance.
Comprehensive 2-Year Warranty
Comes with a full 2-year warranty to guarantee long-term reliability and user confidence.

Details

Emergency Stop available to instantly eliminate hazards
Emergency Stop available to instantly eliminate hazards
Multiple warning protections: water level alarm, over-temperature alarm, water flow alarm...
Thermal insulation for water tubing, pump and evaporator.
Fully hermetic compressor with built-in motor protection.
Temperature controller
Display water temperature
of laser & optics cooling circuits Temperature stability of ±1℃
Stainless steel filter
Recyclable and anti-clogging
Water pressure gauge
Display of water pump status and water pressure
Waterproof junction box
Safe and stable, flexible power cable installation
Premium axial fan
Quiet, efficient heat dissipation and maintenance-free
Double-effect heating
Plate heat exchanger and heater to achieve efficient heating to prevent condensation.

Certificate

Working principle

Ventilation Distance

FAQ

1
Is TEYU Chiller a trading company or a manufacturer?
We are professional industrial chiller manufacturer since 2002.
2
What is the recommended water used in the industrial water chiller?
The ideal water should be deionised water, distilled water or purified water.
3
How often should I change out the water?
Generally speaking, the water changing frequency is 3 months. It can also depend on the actual working environment of the recirculating water chillers. For example, if the working environment is too inferior, the changing frequency is suggested to be 1 month or shorter.
4
What is the ideal room temperature for the water chiller?
The working environment of the industrial water chiller should be well ventilated and the room temperature should not be higher than 45 degree C.
5
How to prevent my chiller from freezing?
For users living in high latitude areas especially in winter, they often face the frozen water problem. To prevent the chiller from freezing, they can add an optional heater or add anti-freezer in the chiller. For detailed use of the anti-freezer, it is suggested to contact our customer support team (service@teyuchiller.com) first.

We're here for you when you need us.

Please complete the form to contact us, and we'll be happy to help you.

Ikhaya   |     Imikhiqizo       |     I-SGS & UL Chiller       |     Isixazululo Sokupholisa     |     Inkampani      |    Insiza       |      Ukusimama
Ilungelo Lokushicilela © 2026 TEYU S&A Chiller | Imephu Yesayithi Inqubomgomo Yobumfihlo
Xhumana nathi
email
Xhumana nenkonzo yamakhasimende
Xhumana nathi
email
hlikihla
Customer service
detect