S&A Teyu compressor air cooled water chiller CW-6000 has T-506 temperature controller (defaulted as intelligent temperature control mode). To change the T-506 temperature controller to constant temperature mode, please follow the steps below:
1.
Press and hold “▲” button and “SET” button for 5 seconds;
2.
Until the upper window indicates “00” and the lower window indicates “PAS”
3.
Press “▲” button to select the password “08”. (Default setting is 08)
4.
Press “SET” button to enter menu setting
5.
Press “▶”button until the lower window indicates F3(F3 stands for way of control)
6.
Press “▼” button to change the data in upper window from 1 to 0. (1 means intelligent temperature control mode while 0 means constant temperature mode)
7.
Press “RST” button to save the modification and exit setting