How to switch S&A compressor air cooled water chiller CW-6000 from intelligent control mode to constant control mode?

laser cooling

S&A Teyu compressor air cooled water chiller CW-6000 has T-506 temperature controller (defaulted as intelligent temperature control mode). To change the T-506 temperature controller to constant temperature mode, please follow the steps below:

1. Press and hold “▲” button and “SET” button for 5 seconds;

2. Until the upper window indicates “00” and the lower window indicates “PAS”

3. Press “▲” button to select the password “08”. (Default setting is 08)

4. Press “SET” button to enter menu setting

5. Press “▶”button until the lower window indicates F3(F3 stands for way of control)

6. Press “▼” button to change the data in upper window from 1 to 0. (1 means intelligent temperature control mode while 0 means constant temperature mode)

7. Press “RST” button to save the modification and exit setting