Njengoko ubushushu basehlotyeni busebenza ngokupheleleyo, ii-industrial chillers —izixhobo zokupholisa ezibalulekileyo kwiindawo ezininzi zoshishino—zidlala indima ebalulekileyo ekuqinisekiseni imigca yemveliso egudileyo. Kwiindawo ezishushu, ii-industrial chillers zingenza imisebenzi eyahlukeneyo yokuzikhusela, njenge-E1 ultrahigh room temperature alarm, ukuqinisekisa imveliso ekhuselekileyo. Esi sikhokelo siya kukunceda ukusombulula ingxaki ye-E1 alarm kwi-TEYU S&A's industrial chillers:
Isizathu esinokwenzeka 1: Ubushushu obuphezulu kakhulu
Cinezela iqhosha elithi “▶” kwisilawuli ukuze ungene kwimenyu yokubonisa imeko kwaye ujonge ubushushu obuboniswe yi-t1. Ukuba ikufutshane ne-40°C, ubushushu be-ambient buphezulu kakhulu. Kucetyiswa ukuba kugcinwe ubushushu begumbi phakathi kwe-20-30°C ukuqinisekisa ukuba i-industrial chiller isebenza ngokuqhelekileyo.
Ukuba ubushushu obuphezulu beworkshop buchaphazela i-industrial chiller, cinga ngokusebenzisa iindlela zokupholisa ezibonakalayo ezifana neefeni ezipholiswe ngamanzi okanye iikhethini zamanzi ukunciphisa ubushushu.
Unobangela wesi-2: Umoya onganelanga ojikeleze i-Industrial Chiller
Qinisekisa ukuba kukho indawo eyaneleyo ejikeleze indawo yokungena komoya kunye nendawo yokukhupha umoya kwi-industrial chiller. Indawo yokukhupha umoya kufuneka ibe yimitha eyi-1.5 ukusuka kuyo nayiphi na imiqobo, kwaye indawo yokungenisa umoya kufuneka ibe yimitha eyi-1 ukusuka kuyo, ukuqinisekisa ukutshatyalaliswa kobushushu okufanelekileyo.
Unobangela onokwenzeka wesi-3: Ukuqokelelwa kothuli olunzima ngaphakathi kwi-Industrial Chiller
Ehlotyeni, ii-industrial chillers zisetyenziswa rhoqo, nto leyo ebangela ukuba uthuli luqokeleleke lula kwii-filter gauzes kunye nee-condenser. Zicoce rhoqo kwaye usebenzise i-air gun ukuze uvuthuze uthuli oluvela kwii-condenser fins. Oku kuya kuphucula ngempumelelo ukusebenza kakuhle kwe-industrial chiller ekususeni ubushushu. (Okukhona amandla e-industrial chiller emakhulu, kokukhona kufuneka ucoce rhoqo.)
Unobangela onokwenzeka 4: Isivamvo sobushushu begumbi esingalunganga
Vavanya isenzi sobushushu begumbi ngokusibeka emanzini anobushushu obaziwayo (obucetyiswayo yi-30°C) kwaye ujonge ukuba ubushushu obubonisiweyo buhambelana nobushushu bokwenyani. Ukuba kukho ukungangqinelani, isenzi sinempazamo (isenzi sobushushu begumbi esinempazamo sinokubangela ikhowudi yempazamo ye-E6). Kule meko, isenzi kufuneka sitshintshwe ukuqinisekisa ukuba i-industrial chiller inokubona ngokuchanekileyo ubushushu begumbi kwaye ilungise ngokufanelekileyo.
Ukuba usenemibuzo malunga nokugcinwa okanye ukusombulula iingxaki TEYU S&A's industrial chillers, nceda ucofe kwiChiller Troubleshooting , okanye unxibelelane neqela lethu emva kokuthengisa apha.service@teyuchiller.com .
![Ungayisombulula njani impazamo ye-E1 Ultrahigh Room Temperature Alarm kwi-Industrial Chillers?]()