Ngobushushu basehlotyeni, i-industrial chillers -izixhobo ezibalulekileyo zokupholisa kwiinkqubo ezininzi zemizi-mveliso-zidlala indima ebalulekileyo ekuqinisekiseni imigca yemveliso egudileyo. Kwiindawo ezishushu, i-industrial chillers inokuqalisa imisebenzi eyahlukeneyo yokuzikhusela, njenge-alamu ye-E1 ye-ultrahigh yeqondo lokushisa, ukuqinisekisa imveliso ekhuselekileyo. Esi sikhokelo siya kukunceda ukuba uxazulule ingxaki ye-alamu ye-E1 kwi-TEYU S&A's chillers industrial:
Unobangela woku-1: Ubushushu obuphezulu be-Ambient
Cinezela iqhosha elithi “▶” kwisilawuli ukuze ufake imo yemenyu yokubonisa kwaye ujonge ubushushu obuboniswe ngu-t1. Ukuba isondele kuma-40°C, ubushushu be-ambient buphezulu kakhulu. Kuyacetyiswa ukuba ugcine ubushushu begumbi buphakathi kwe-20-30°C ukuqinisekisa ukuba i-industrial chiller isebenza ngokwesiqhelo.
Ukuba amaqondo obushushu aphezulu eworkshop achaphazela i-industrial chiller, cinga ukusebenzisa iindlela zokupholisa ngokomzimba ezifana neefeni ezipholileyo ngamanzi okanye iikhethini zamanzi ukunciphisa ubushushu.
Unobangela onokwenzeka wesi-2: Ukungena komoya okungonelanga kwi-Industrial Chiller
Khangela ukuba kukho indawo eyaneleyo ejikeleze indawo yokungenisa umoya kunye nendawo yokuphuma yesibandisi seshishini. I-air outlet kufuneka ibe ubuncinane i-1.5 yeemitha ukusuka kuyo nayiphi na imiqobo, kwaye i-air inlet kufuneka ibe ubuncinane imitha eyi-1, iqinisekise ukuchithwa kobushushu.
Unobangela wesi-3 onokwenzeka: Ukuqokelelwa kothuli olunzima Ngaphakathi kwi-Industrial Chiller
Ehlotyeni, ii-chillers zamashishini zisetyenziswa rhoqo, zibangela ukuba uthuli luqokelele ngokulula kwi-gauzes yokucoca kunye ne-condensers. Zicoce rhoqo kwaye usebenzise umpu womoya ukuvuthela uthuli olusuka kumaphiko econdenser. Oku kuya kuphucula ngempumelelo i-industrial chiller yokuphelisa ubushushu. (Okukhona usiba makhulu amandla e-industrial chiller, kokukhona kufuneka ucoce rhoqo.)
Unobangela we-4: Isixhobo soVavanyo lobushushu begumbi esinempazamo
Ukuvavanya inzwa yeqondo lokushisa kwegumbi ngokuyibeka emanzini kunye nokushisa okwaziwayo (okucetywayo kwi-30 ° C) kwaye khangela ukuba iqondo lokushisa elibonisiweyo lihambelana neqondo lokushisa langempela. Ukuba kukho ukungafani, i-sensor iphosakele (i-sensor yeqondo lokushisa eliphosakeleyo lingabangela ikhowudi yephutha ye-E6). Kule meko, i-sensor kufuneka itshintshwe ukuze kuqinisekiswe ukuba i-chiller ye-industrial iyakwazi ukubona ngokuchanekileyo ubushushu begumbi kwaye ilungelelanise ngokufanelekileyo.
Ukuba usenemibuzo malunga nokugcinwa okanye ukulungisa iingxaki kwi-TEYU S&A ye-industrial chillers, nceda ucofe iChiller Troubleshooting , okanye uqhagamshelane neqela lethu emva kokuthengisaservice@teyuchiller.com .
![Indlela yokuSombulula iFault ye-Alarm yeGumbi le-E1 ye-Ultrahigh kwi-Industrial Chillers?]()