loading

If the water tank temperature of water chiller is too high, is it useful to add Freon

A customer of S&A Teyu consults to S&A Teyu: “Hello,if the CW-5200 water chiller stops working due to over-high temperature of water tank,is it useful to add Freon?”

laser cutting

A customer of S&A Teyu consults to S&A Teyu: “Hello, if the CW-5200 water chiller stops working due to over-high temperature of water tank, is it useful to add Freon?”

Here, S&A Teyu reminds all customers: over-high temperature of water tank of the water chiller is not necessarily caused by refrigerant leakage. The reasons for over-high temperature of water tank of the water chiller include the following points:

1. If the dust screen is blocked, it is only needed to clean the dust screen;

2. If the place where the water chiller is located is unventilated, it is only needed to ensure smooth air-in and air-out channels of the water chiller;

3. If the water chiller has dust deposition inside, it is only needed to clear the dust deposition inside the water chiller;

4. If the fan of the water chiller stops rotating, it is only needed to replace the fan;

5. If the starting capacitance of the compressor declines, it is only needed to replace the capacitor;

6. If the voltage of power supply for the water chiller is not stable, it is only needed to add a voltage regulator;

If the six possible reasons above are excluded, the reason may be refrigerant leakage of the water chiller. It is needed to check and fill up the point that has refrigerant leakage and to refill refrigerant.

Thank you so much for your support and trust in S&A Teyu. All S&A Teyu water chillers have passed the certification of ISO, CE, RoHS and REACH, and the warranty is 2 years. Welcome to purchase our products!

water chiller

We're here for you when you need us.

Please complete the form to contact us, and we'll be happy to help you.

Home       Products          SGS & UL Chiller       Cooling Solution       Company       Resource       Sustainability
Copyright © 2025 TEYU S&A Chiller | Sitemap    Privacy policy
Contact us
email
Contact customer service
Contact us
email
cancel
Customer service
detect