Chiller Maintenance Videos
Watch practical video guides on operating, maintaining, and troubleshooting TEYU industrial chillers. Learn expert tips to ensure optimal performance and extend the lifespan of your cooling system.
How to replace the DC pump for industrial water chiller CW-5200?
This video will teach you how to replace the DC pump of S&A industrial chiller 5200.First to turn off the chiller, unplug the power cord, uncap the water supply inlet, remove the upper sheet metal housing, open the drain valve and drain water out of the chiller, disconnect the DC pump terminal, use a 7mm wrench and a cross screwdriver, unscrew the 4 fixing nuts of the pump, remove the insulated foam, cut off the zip cable tie of the water inlet pipe, unfasten the plastic hose clip of the water outlet pipe, separate water inlet and outlet pipes from the pump, take out the old water pump and install a new pump on the same position, connect the water pipes to the new pump, clamp the water outlet pipe with a plastic hose clip, tighten 4 fixing nuts for the water pump base. Lastly, connect the pump wire terminal, and the DC pump replacement is finally finished.
2023 02 14
How to solve the laser circuit flow alarm of the industrial water chiller?
What to do if the laser circuit’s flow alarm rings? First, you can press the up or down key to check the flow rate of the laser circuit. Alarm will be triggered when the value falls below 8, it may be caused by the Y-type filter clogging of the laser circuit water outlet.Turn off the chiller, find the Y-type filter of the laser circuit water outlet, use an adjustable wrench to remove the plug anticlockwise, take out the filter screen, clean and install it back, remember not to lose the white sealing ring on the plug. Tighten the plug with wrench, if the flow rate of laser circuit is 0, it is possible that the pump is not working or the flow sensor fails. Open the left-side filter gauze, use a tissue to check whether the back of the pump will aspirate, if the tissue is sucked in, it means the pump is working normally, and there may be something wrong with the flow sensor, feel free to contact our after-sales team to solve it. If pump is not working properly, open the electric box, me...
2023 02 06
How to deal with water leakage of the industrial chiller’s drain port?
Having closed the chiller’s water drain valve, but the water still keeps running at midnight...Water leakage still occurs after the chiller drain valve is closed.This may be that the valve core of the mini valve is loose.Prepare an allen key, aiming at the valve core and tighten it clockwise, then check the water drain port. No water leakage means the problem is solved. If not, please contact our after-sales team immediately.
2023 02 03
How to replace the flow switch for the industrial water chiller?
First to turn off the laser chiller, unplug the power cord, uncap the water supply inlet, remove the upper sheet metal housing, find and disconnect the flow switch terminal, use a cross screwdriver to remove the 4 screws on the flow switch, take out the flow switch top cap and the internal impeller. For the new flow switch, use the same method to remove its top cap and impeller. then install the new impeller into the original flow switch. Use the cross screwdriver to tighten the 4 fixing screws, reconnect the wire terminal and you’re done~Follow me for more tips on chiller maintenance.
2022 12 29
How to check the room temperature and flow of industrial water chiller?
Room temperature and flow are two factors that greatly affect the industrial chiller cooling capacity. Ultrahigh room temperature and ultralow flow will affect the chiller cooling capacity. The chiller works at room temperature above 40 ℃ for a long time will cause damage to the parts. So we need to observe these two parameters in real time.First, when the chiller is turned on, take the T-607 temperature controller as an example, press the right arrow button on the controller, and enter the status display menu. "T1" represents the temperature of the room temperature probe, when the room temperature is too high, the room temperature alarm will set off. Remember to clean up the dust to improve ambient ventilation. Continue to press the "►" button, "T2" represents the flow of the laser circuit. Press the button again, "T3" represents the flow of the optics circuit. When detected a traffic drop, the flow alarm will set off. It is time to replace the circulating water, and clean the filt...
2022 12 14
How to replace the heater of the industrial chiller CW-5200?
The main function of the industrial chiller heater is to keep the water temperature constant and prevent cooling water from freezing. When the cooling water temperature is lower than the set one by 0.1℃, the heater starts to work. But when the heater of the laser chiller fails, do you know how to replace it?First, turn off the chiller, unplug its power cord, uncap the water supply inlet, remove the sheet metal casing, and find and unplug the heater terminal. Loosen the nut with a wrench and take out the heater. Take down its nut and rubber plug, and reinstall them on the new heater. Lastly, insert the heater back into the original place, tighten the nut and connect the heater wire to finish.
2022 12 14
How to replace the cooling fan of the industrial chiller CW 3000?
How to replace the cooling fan for CW-3000 chiller?First, turn off the chiller and unplug its power cord, uncap the water supply inlet, unscrew the fixing screws and remove the sheet metal, cut off the cable tie, distinguish the cooling fan’s wire and unplug it. Take away fixing clips on both sides of the fan, disconnect the fan’s ground wire, untighten the fixing screws to take out the fan from the side. Watch carefully the airfow direction when installing a new fan, don't install it backwards because the wind is blowing out of the chiller. Assemble the parts back the way you disassemble them. It is better to organize wires using a zip cable tie. Lastly, assemble the sheet metal back to finish.What else do you want to know about the maintenance of the chiller? Welcome to leave a message to us.
2022 11 24
Water temperature of laser remains high?
Try replacing the cooling fan capacitor of the industrial water chiller!First, remove the filter screen on both sides and the power box panel. Don't get it wrong, this is the compressor starting capacitance, which needs to be removed, and the hidden one inside is the starting capacitance of cooling fan. Open the trunking cover, follow capacitance wires then you can find the wiring part, use a screwdriver to unscrew the wiring terminal, the capacitance wire can be easily taken out. Then use a wrench to unscrew the fixing nut on the back of power box, after which you can take off the starting capacitance of the fan. Install the new one on the same position, and connect wire at the corresponding position in the junction box, tighten the screw and the installation is completed.Follow me for more tips on the chiller maintenance.
2022 11 22
What to do if the flow alarm rings in the industrial chiller CW 3000?
What to do if the flow alarm rings in the industrial chiller CW 3000? 10 seconds to teach you to find the causes.Firstly, turn off the chiller, remove the sheet metal, unplug the water inlet pipe, and connect it to the water supply inlet. Turn on the chiller and touch the water pump, its vibration indicates the chiller works normally. Meanwhile, observe the water flow, if the water flow decreases, please immediately contact our after-sales staff.Follow me for more tips on the maintenance of chillers.
2022 10 31
Industrial Chiller CW 3000 Dust Removal
What to do if there is dust accumulation in the industrial chiller CW3000?10 seconds to help you solve this problem. First, remove the sheet metal, then use an air gun to clean the dust on the condenser. The condenser is an important cooling part of the chiller, and periodic dust cleaning is conducive to stable cooling. Follow me for more tips on chiller maintenance.
2022 10 27
Industrial chiller cw 3000 fan stops rotating
What to do if the cooling fan of the chiller CW-3000 does not work?This may be caused by the low ambient temperature. The low ambient temperature keeps the water temperature below 20 ℃, thus leading to its malfunction. You can add some warm water through the water supply inlet, then remove the sheet metal, find the wiring terminal beside the fan, then re-plug the terminal and check the operation of the cooling fan. If the fan is rotating normally, the fault is solved. If it still does not rotate, please immediately contact our after-sales staff.
2022 10 25
Industrial Chiller RMFL-2000 Dust Removal And Water Level Checking
What to do if there is dust accumulation in the chiller RMFL-2000? 10 seconds to help you solve the problem.First to remove the sheet metal on the machine, use the air gun to clean the dust on the condenser. The gauge indicates the water level of the chiller, and water filled to the range between the red and yellow area is recommended.Follow me for more tips on the maintenance of chillers.
2022 10 21